Cybrotech GSM-1 Manual de usuario Pagina 14

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 32
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 13
230V~
230VAC
Internal CyBro power supply has enough power for 3-4 external modules. Bigger systems should
use external power supply.
IEX-2 power supply
1) Small system - CyBro-2-230 internal power supply
2) Large system - CyBro-2-24 + external power supply
Total power output for IEX-2 modules is limited to 2A because
of RJ-9 connector. If more current is needed, additional IEX-2
modules may be connected using bus extender (BE).
Each IEX-2 module has unique network address, labeled on side.
Bio-24 AiR-12 OP-2
CyBro-2
In A-bus/RS485 network, first and the last CyBro-2 should have termination switch set to on. All others
should have termination switch set to off.
CyBro
A-bus
CyBro CyBro CyBro CyBro
termination ON termination OFF termination OFF termination OFF termination ON
IEX-2 addressing
A-bus termination
Slot 0 1 2 3
NAD 2821 2143 2524
Bio-24R: 160mA
AiR-12: 50mA
OP-2: 40mA
CyBro inputs: 8x7mA=56mA
Bio-24 inputs: 12x7mA=84mA
Total consumption: 440mA
AiV-12: 50mA
12
Example:
230V~
24V=
24VDC
Vista de pagina 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 31 32

Comentarios a estos manuales

Sin comentarios